NVIDIA H200 Disassembly & Liquid-Cooling Installation with EK-Pro H200 NVL Water Block
Mirrored from r/LocalLLaMA for archival readability. Support the source by reading on the original site.
| This is a full teardown video of the NVIDIA H200 NVL and installation of an EK-Pro H200 NVL Water Block, covering the disassembly, prep and mount process, including:
Once assembled, it undergoes a 24-hour leak test with the pump powered independently, allowing for leak detection with no risk to the PCB, before stress testing the GPU under load to ensure maximum sustained performance. We currently deploy up to 8x H200 GPUs custom liquid-cooled, in the LM TEK RM-4U8G server rack. In testing, a fully populated 8x H200 liquid-cooled server rack draws around 6,800–7,000W under sustained load including CPU and cooling solution. Stress-tested at 30°C ambient, it holds GPU package temps at 76–81°C under full load across all 8 GPUs, with the platform rated up to 35°C ambient. [link] [comments] |